High/Low level switches used for automatic filling of a
tank.This is a simple level control application using two Babbitt LS7000 level switches to control automatic filling of a tank. The tank could be an open hopper, a pressure vessel, or a sump. The material being controlled could be plastic pellets, grain, crude oil or boiling acid. The concept is the same for all.
When the level falls to point "A", the pump turns on. The pump continues to run until the level rises to point "B" and then turns off.
The pump motor starter is activated by 115VAC control voltage at the Level
Switch "A" #1 relay contacts. Wiring terminations are made between Common
(C1) and and Normally Closed (NC1). The switch is set at "Fail-Safe Low",
which means that it will de-energize the relay output upon absence of
material (liquid or bulk solid) at the probe, and energize the relay upon
presence of material at the probe.
Level Switch "A" will energize (opening up the NC contact) as the level rises and touches the probe. To keep the pump running as the level rises, the Auxiliary Contact of the pump motor starter is used to seal-in the run command to itself.
Level Switch "B" is set for "Fail-Safe High" (energize upon absence of material at the probe) with the wiring terminations made between Common (C1) and Normally Open (NO1) on the #1 relay contacts. Level Switch "B" must energize the relay output to enable the pump to run. When the level rises to point "B", Level Switch "B" will de-energize, and shut off the pump motor.
This Fail-Safe logic is used to prevent accidental overfill if Level Switch B's wiring is cut or relay contacts are burned.
Advantages:
Pricing: $700 to $1000, depending on probe length and material, for two switch system.
We invite you to contact us with your next application.